beautypg.com

Technical data – REMKO GPM 15 User Manual

Page 43

background image

43

Technical data

Series

GPM 15

GPM 25

GPM 35

GPM 55

GPM 75

min.

max.

min.

max.

min.

max.

min.

max.

min. max.

Nominal heating capacity

kW

12.5

16.5

20.0

26.5

24.0

34.8

40.0

58.0

58.0 78.0

Nominal heat output

kW

11.8

15.1

18.8

24.4

22.6

31.5

37.6

53.0

54.5 71.5

Nominal air volume flow

m

3

/h

2450

3050

3050

6250

6800

Fuel

Natural gas or LPG

CO2 content

1)

%

8.7 ± 0.2

Exhaust flow rate

1)

kg/h

22

30

35

46

42

61

70

101

102

136

CO2 content

2)

%

9.4 ± 0.2

Exhaust flow rate

2)

kg/h

23

31

36

48

43

62

72

103

104

140

Exhaust gas temperature about

°C

190

200

210

195

190

Efficiency

%

94.0

91.8

94.0

91.9

94.0

90.5

94.0

91.4

94.0 91.7

Gas connection

Inch

¾“

¾“

¾“

¾“

1“

Air temperature increase

K

21.1

27.0

18.0

23.4

21.7

30.2

17.6

24.8

23.5 30.8

Gas flow rate (nat. gas H)

3)

m

3

/h 1.32

1.75

2.12

2.80

2.54

3.68

4.23

6.14

6.14 8.25

Gas flow rate (nat. gas L)

3)

m

3

/h 1.54

2.03

2.46

3.26

2.95

4.28

4.92

7.13

7.13 9.59

Gas flow rate (LPG)

3)

kg/h 0.79

1.05

1.27

1.68

1.52

2.21

2.54

3.68

3.68 4.95

Necessary chimney draft

Pa

0

Avail. pressure exhaust gas side

Pa

50

50

90

120

120

Sound pressure level LpA 5m

dB(A)

42.9

46.9

46.9

50.5

50.5

Power supply

V/Hz

230/1~/50

Nominal current

A

0.61

1.13

1.13

1.91

1.91

Power consumption

W

140

260

260

440

440

Combustion air connection

mm

80 Ø

80 Ø

80 Ø

80 Ø

100 Ø

Chimney connection

mm

80 Ø

80 Ø

80 Ø

80 Ø

100 Ø

Installation variants

Type

B23 / C13 / C33 / C43 / C53 / C63

EC approval

No.

0694BN4077

Weight

kg

59

65

69

97

150

We reserve the right to make changes to dimensions and design in the interest of technological advances.

1)

Values for burning natural gas

2)

Values for burning LPG

3)

Values based on 15°C-1013mbar

This manual is related to the following products: