REMKO GPM

Gas connection

LEGEND
1 = Electric gas solenoid valve

Main burner

2 = Electric gas solenoid valve

Ignition burner

3 = Pressure regulator
4 = Electric gas safety valve
5 = Gas filter (small filter area)
6 = Vibration absorbing

connecting piece (locally)

7 = Gas filter with large filter area

(locally)

8 = Gas shut-off valve (locally)

1

2

3

4

5

6

7

8

Arrangement of factory supplied gas components

must be installed by the
installation company

Installation of the gas connection
must only take place by authorised
specialists (approved by the gas
supply company) in compliance
with the regulations applicable to
the respective type of gas.
The cross-section of the cables
must be dimensioned according
to the installed load of the unit,
total line resistance and gas supply
pressure.
The necessary gas supply pressure
(depending on the particular type
of gas) must be ensured locally.
Depending on the capacity of the
unit, the necessary gas volume
and gas pressure must be available
constantly during operation.
Connection of the unit takes place
via a R 3/4“ or R 1“ connection
with external thread.
The gas supply pipe must be
installed stress and vibration-free
using suitable, detachable unions.
The components prescribed in
the pertinent gas directives and
necessary components in the gas
pipe locally must be installed by a
qualified installation company.

Gas pressure reducers, shut-off
devices, etc., are not included in
the factory delivery and must be
provided locally.
The installation of a gas filter
without pressure regulator is also
recommended as the area of the
standard filter installed above the
gas valve is limited.
The applicable standards allow
within rooms or heating rooms a
maximum pressure of 60 mbar;
higher pressures must be reduced
prior to admission into the heating
room or room in which the unit is
installed.
Before using the unit for the first
time, the gas supply pipe must be
thoroughly cleaned and vented by
suitable means.
It must be ensured that the unit
is connected gas-tight to the gas
supply pipe.
All screwed connections of the unit
and gas pipe must be checked for
tightness.
If leak detection sprays are used,
these must comply with DIN
30657 (corrosion-free).

We reserve the right to make changes to dimensions and design in the interest of technological advances.

ATTENTION

Installation of the gas system
and supply pipes must only
be carried out by authorised
specialists.