Remko gpm, Chimney connection – REMKO GPM 15 User Manual
Page 22
22
REMKO GPM
Ceiling suspension
A ceiling installation set with horizontal air
outlet is available as an
accessory for suspending the units using eyebolts. EDP No: 228765
Vertical air flow
Suspension of the units using
eyebolts with the air flow directed
downwards (installation with
vertical air flow).
A ceiling installation set with
vertical air outlet
is available as an
accessory for this purpose.
It consists of eyebolts with special
fastener and additional fan
thermostats.
EDP No: 228766 to GPM 35
EDP No: 228767 from GPM 55
We reserve the right to make changes to dimensions and design in the interest of technological advances.
Additional thermostat for
fan monitoring
The units operate in a closed
combustion system.
The fan is located upstream of the
heat exchanger.
The chimney duct and combustion
air supply must be planned and
executed in compliance with the
respective local regulations.
For outside wall installations, the
local master chimney sweep must
previously be consulted.
The various types of installation
are classified according to the
European standard EN 1020 and
DVGW-TRGI Directive 2008 and in
the factory supplied variant is part
of the EC approval.
The units are classified for the
following individual variants:
B23/C13/C33/C43/C53/C63
The chimney and air supply pipes
can be installed in different ways.
For example: Gas appliance type
B:
The combustion system is not tight
with respect to the environment in
which it is installed.
The combustion air is extracted
directly from the installation room.
This variant may only be installed
in rooms having at least one
door leading to the outside or
one window that can be opened
and having a cubic capacity of
minimum 4 m
3
per kW total
nominal heat output of the unit or
a combustion air opening leading
to the outside of minimum 150
cm
2
or two openings each having
a minimum free cross-section of 75
cm
2
.
Chimney connection
s
s
s