REMKO GPM 15 User Manual
Page 25

25
Type C13 horizontal/coaxial
L1 + L2 maximum pipe length
without end pieces
ø 80
ø 100
Model
Metres
GPM15
10 + 10
GPM25
10 + 10
GPM35
10 + 10
GPM55
4.5 + 4.5
GPM75
4 + 4
Type C33 vertical/coaxial
L1 + L2 maximum pipe length
without end pieces
ø 80
ø 100
Model
Metres
GPM15
11 + 11
GPM25
11 + 11
GPM35
11 + 11
GPM55
4.5 + 4.5
GPM75
4 + 4
Gas appliance Type C
Non-roomsealed combustion
system.
The combustion system is tight
with respect to the environment in
which it is installed.
The combustion air is supplied
from the outside.
The pipes run horizontally through
the outside wall or vertically via
the roof.
L1
KO
L2
Mounting height
Side view
2.5 - 3.5 m
L1
L2
Mounting height
2.5 - 3.5 m
Side view
L1
L2
Mounting height
2.5 - 3.5 m
Front view
Type C33
Non-roomsealed combustion
system.
The chimney and combustion air
ducting is routed via the roof using
a LAS end piece.
Type C13
Non-roomsealed combustion
system.
The chimney and combustion
air ducting is routed through the
outside wall using a LAS end piece.
We reserve the right to make changes to dimensions and design in the interest of technological advances.
Condensate connection [KO] =
M 30 external thread
NOTE
The installation of chimney
pipes through outside walls
must comply with the
requirements of DVGW - TRGI
and TRF and be approved
by the local master chimney
sweep.
NOTE
With this type of unit, the
position of the connections
on the unit must be changed,
i.e. they must be routed from
the rear upwards.
This variant
is provided at the factory
and must be specified when
ordering.
NOTE