24

REMKO GPM

Type B23 horizontal

L1 maximum pipe length without

end pieces

ø 80

ø 100

Model

Metres

GPM15

29

GPM25

29

GPM35

26

GPM55

15

GPM75

18

Type B23 vertical

L1 maximum pipe length without

end pieces

ø 80

ø 100

Model

Metres

GPM15

30

GPM25

30

GPM35

29

GPM55

17

GPM75

20

Installation examples

Gas appliance type B23

Non-roomsealed combustion
system

The combustion system is not tight
with respect to the environment
in which it is installed. The
combustion air is extracted directly
from the installation room.
There are two options for
installation of the chimney ducting:

a) with the aid of a horizontal

pipe (outside wall installation)
straight through the outside wall
or

b) if the roof is simultaneously the

ceiling, with a vertical pipe via
the roof.

With this installation option,
adequate ventilation of the
installation room must be ensured
in order to provide a correct
combustion air supply.
This takes place by means of
openings in the room walls.
The dimensions and characteristics
defined in applicable standards
must be observed.
In particular, DVGW-TRGI 2008
Section 5.2.2. and TRF Section
7.2.2. must be observed.

The combustion air supply must
always take place from the
outside:

for mechanical extraction

systems in the installation room

if excess or low pressure can

occur in the installation room

if the unit is installed in

environments subject to high
dust development

in garages

With this type of unit, a
protective grille must be
provided on the combustion
air supply pipe in order to
prevent the ingress of solid
bodies with a diameter above
12 mm.

ATTENTION

Combustion air inlet grille [S]
GPM 15 - 55; EDP No: 228960
GPM 75

EDP No: 229060

L1

Mounting height

2.5 - 3.5 m

S

Side view

L1

Mounting height

2.5 - 3.5 m

Side view

S

K

Type B23 horizontal through the
outside wall

Type B23 vertical through the
ceiling

We reserve the right to make changes to dimensions and design in the interest of technological advances.

Condensate connection [K] =

M 20 external thread

NOTE