3.1. Device Object:
The Device object default property values are as follows –
Property Name
Default Values
object-identifier
7
object-name
Device,1
object-type
Device
system-status
operational
vendor-name
ONICON, Incorporated
vendor-identifier
206
model-name
Vortex Meter
firmware-revision
N/A
application-softwareversion
1.07
protocol-version
1
protocol-revision
4
protocol-servicessupported
{F,F,F,F,F,F,F,F,F,F,F,F,T,F,T,T,T,T,F,F,F,F,F,F,F,F,F,F,F,F,T,T,F,F,F,F,F}
protocol-object-types-supported
{T,F,F,T,F,T,F,F,T,F,F,F,F,F,F,F,F,F,F,F,F,F,F,F,F}
object-list
{(analog-input,1), (analog-input,2), (analog-input,3), (analog-
input,4), (analog-input,5), (analog-input,6), (analog-input,7), (analog-
input,8) (analog-input,9), (analog-input,10), (analog-input,11),
(analoginput,12), (analog-input,13), (analog-input,14), (analoginput,
15), (analog-input,16), (analog-input,17), (analoginput, 18), (analog-
input,19), (binary-input,1), (binary-input,2), (binaryinput,3), (binary-
input,4), (binary-value,1), (device,7) }
max-apdu-lengthaccepted
300
segmentation-supported
no-segmentation
apdu-timeout
3000
number-of-APDU-retries
1
max-master
127
max-info-frames
1
device-address-binding
()
database-revision
0
Note - Device Communication Control: Password – “vortek”
4.3.3.2. Analog Input Object:
Vortex Mass Flow Meters Analog Input type objects are described
in the below Table –
Object Instance
Object Name
Unit
Description
1
Volume Flow
cubic-feet-per-second, cubic-feet-per-
minute, us-gallons-per-minute, imperial-
gallons-perminute, liters-per-minute,
liters-per-second, liters-per-hour, cubic-
meters-per-second, cubic-meters-per-
minute, cubic-meters-per-hour
This AI object is used to
measure volume flow.