Warning – ONICON F-2600 User Manual
Page 71
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204
Page 71
SECTION 4.0: SERIAL COMMUNICATIONS
4.1 HART COMMUNICATIONS
The HART Communications Protocol (Highway Addressable Remote Transducer Protocol) is a
bidirectional digital serial communications protocol. The HART signal is based on the Bell 202
standard and is superimposed on 4-20 mA Output 1. Peer-to-peer (analog / digital) and multi-drop
(digital only) modes are supported.
4.1.1 WIRING
The diagrams below detail the proper connections required for HART communications:
Loop Powered Meter Wiring
LOOP
POWER
+
-
FREQ OUT
PULSE OUT
-
-
+
+
OPTIONAL BACKLIGHT POWER +
-
R load,
250 ohm
minimum
+
_
DC
Power
Supply
Remote Connection
for Communicator
Current
Meter
Field Connection
for Communicator
Vortex Meter
Figure 50. Loop Powered Meter Wiring (HART)
!
WARNING
Place controls in manual mode when making configuration changes to the vortex meter.