Control Register Definitions

The only writeable registers in this implementation are the Reset Exception Status, Reset
Meter and Reset Totalizer functions, which are implemented as ”coils” which may be
written with the Write Single Coil command (function code 05) to address 8 through 10,
respectively (register #00009 through #00011). The value sent with this command must be
either 0x0000 or 0xff00, or the meter will respond with an error message. The totalizer will
be reset or exception status cleared only with a value of 0xff00.

Error Responses

If an error is detected in the message received by the unit, the function code in the
response is the received function code with the most significant bit set, and the data field
will contain the exception code byte as follows:

Exception

Code

Description

01

Invalid function code — function code not supported by device

02

Invalid data address — address defined by the start address and
number of registers is out of range

03

Invalid data value — number of registers = 0 or >125 or incorrect
data with the Write Single Coil command

If the first byte of a message is not equal to the unit’s Modbus address, if the unit detects a
parity error in any character in the received message (with even or odd parity enabled), or
if the message CRC is incorrect, the unit will not respond.

Command Message Format

The start address is equal to the desired first register number minus one. The addresses
derived from the start address and the number of registers must all be mapped to valid
defined registers, or an invalid data address exception will occur.

Device Address

8 bits, 1...247

Function Code

8 bits

Start Address

16 bits, 0...9998

N=Number of Registers

16 bits, 1...125

CRC

16 bits

Normal Response Message Format

Device Address

8 bits, 1...247

Function Code

8 bits

Byte Count = 2

x N

Data

(N) 16-bit registers

CRC

16 bits


Exception Response Message Format

Device Address

8 bits, 1...247

Function Code

8 bits

Exception Code

8 bits

CRC

16 bits