3.3.7 Energy Menu – For EMS Energy Meters Only

Password

ENTER

Use

keys to access menus.

Energy

Menu

Loc in Sent

Flow

Yes or No

ENTER

Run Mode

Heating

System

Yes or No

% Returned

xxx

Configuration:

There are several possibilities regarding the measurement of water or steam energy given
the location of the meter and the use of a second RTD. The table below summarizes the
possibilities:

Fluid

Meter Location

Second RTD

Measurement

Water

“Sent” Flow Line

“Return” Flow Line

Change in Energy

Water

“Return” Flow Line

“Sent” Flow Line

Change in Energy

Water

“Sent” Flow Line

None

Outgoing Energy

Steam

“Sent” Flow Line

“Return” Flow Line (condensate)

Change in Energy

Steam

“Sent” Flow Line

None

Outgoing Energy

As above, you must properly configure the meter in the Energy Menu.

1. Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the

above table.

2. Heating System? Select Yes for a hot water system used for heating. Select No for a

chilled water system used for cooling. Always select Yes for a steam system.

3. % Returned. Select a number between 0% and 100%. Estimate the amount of water

that returns. It is usually 100%, or can be less than 100% if historical data shows
the amount of makeup water used. If a second RTD is not used, set to 0%. When 0%
is selected, the energy calculation represents the outgoing energy only (no return
energy is subtracted).

i

IMPORTANT NOTICE

The meter ships from the factory assuming 0% return and has a 1000 ohm resistor installed in the

RTD #2 wiring location. This needs to be removed if the meter is to be used in a manner other than