5.8 PRESSURE SENSOR REPLACEMENT (IN-LINE ONLY)

1. For local mounted electronics, remove the electronics stack as previously described. For

remote mount electronics, remove all wires and sensor connectors from the remote feed
through board in the junction box at the meter.

2. Loosen the three set screws at the center of the adapter between the meter and the enclosure.
3. Remove the top half of the adapter to expose the pressure transducer.
4. Remove the transducer and replace it with the new one using appropriate thread sealant.
5. Reassemble in reverse order.

5.9 RETURNING EQUIPMENT TO THE FACTORY

Before returning any flow meter to the factory, you must request a Return Material
Authorization (RMA) number.
To obtain an RMA number and the correct shipping address,
contact customer service at:

727-447-6140 (in the USA).

When contacting customer service, be sure to have the meter serial number and model number
ready.

Please see the Meter Troubleshooting Checklist page 96, for additional items which may help
with problem isolation. When requesting further troubleshooting guidance, please record the
values on the checklist at no flow and during flow if possible.