SECTION 2.0 INSTALLATION
2.1 INSTALLATION OVERVIEW
ONICON F-2600 & F-2700 Vortex Flow Meter installations are simple and straightforward.
Both the in-line and the insertion type flow meter installations are covered in this chapter.
After reviewing the installation requirements given below, see page 21 for in-line installation
instructions. See page 24 for insertion style installation instructions. Wiring instructions begin on
page 38.
2.1.1 Flow Meter Installation Requirements
Before installing the flow meter, verify the installation site allows for these considerations:
1. Line pressure and temperature will not exceed the flow meter rating.
2. The location meets the required minimum number of pipe diameters upstream and
downstream of the sensor head as illustrated in Figure 4.
3. Safe and convenient access with adequate overhead clearance for maintenance
purposes.
4. Verify that the cable entry into the instrument meets the specific standard required for
hazardous area installations.
5. For remote installations, verify the supplied cable length is sufficient to connect the
flow meter sensor to the remote electronics.
Also, before installation, check your flow system for anomalies such as:
• leaks
• valves or restrictions in the flow path that could create disturbances in the flow profile
that might cause unexpected flow rate indications
!
WARNING
Consult the flow meter nameplate for specific flow meter approvals before any hazardous location
installation.