beautypg.com

ONICON F-2600 User Manual

Page 86

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204

Page 86

The floating point registers with values in display units are scaled to the same units as
are displayed, but are instantaneous values that are not smoothed. If display smoothing
is enabled (non-zero value entered in the Display TC item in the Display Menu), then the
register values will not agree exactly with the displayed values.

Exception Status Definitions

The Read Exception Status command (function code 07) returns the exception status byte,
which is defined as follows. This byte may be cleared by setting “coil” register #00003
(function code 5, address 2, data = 0xff00).

Bit(s)

Definition

0-1

Byte order (see Modbus Order on page 2)
0 = 3-2:1-0 1 = 2-3:0-1
2 = 1-0:3-2 3 = 0-1:2-3

2

Temperature sensor fault

3

Pressure sensor fault

4

A/D converter fault

5

Period overflow

6

Pulse overflow

7

Configuration changed

Discrete Input Definitions

The status of the three alarms may be monitored via the Modbus Read Discrete Input
command (function code 02). The value returned indicates the state of the alarm, and will
be #1 only if the alarm is enabled and active. A zero value is transmitted for alarms that
are either disabled or inactive.

Registers

Variable

Function Code Address

10001

Alarm #1 state

02

0

10002

Alarm #2 state

02

1

10003

Alarm #3 state

02

2

This manual is related to the following products: