beautypg.com

Mes2 wiring diagram, Mes2 with optional modbus board, Rs485/ttl – Nortec MES2 User Manual

Page 48

background image

MES2 Wiring Diagram

45 | Troubleshooting

Figure 27: MES2 Wiring Diagram

MES2 with Optional Modbus board

WIRING DIAGRAM
DIAGRAM NUMBER 2553788 Rev. B
DATE August 18, 2010

FILL

DRAIN

1

2

3

RS485/TTL

Install J26 For
Modbus Control

ON

OFF

Drain

1

2

3

Green LED

Yellow LED

2 or 3 electrode cylinder

Contactor

24 Vac

(by others)

L1 L2 L3

Primary

Terminal

Block

(by others)

NOTE: Dotted lines denote wiring by others with the exception of
Primary Voltage Wiring ( PVW ) units which will come with all
primary wiring to the cylinder and 10’ of wiring to run the electrical
back to the contactor

Capacity
adjust

Calibration

(Do not ajust!)

Control Signal

(0-10 Vdc, 2-10 Vdc)

(-)

(+)

24

V

ac

Hot

ON/OFF

Safties

24

V

A

C

Common

Modbus Interface
Board (1509592)

A

B

Common

1509591

Modulation:
Remove J10 for 0-10 VDC
Remove Jumper J10 and place it on J13 for 2-10VDC

R52

J7

J6

J5

J4

J3

J2

J1

Mains Voltage

Select Jumpers

J6

208V

J5

230V

J4

277V

J3 380-415V
J2

460V

J1

575V

HW Sensor Jumpers

J9 Low Voltage 200-277V
J8 High Voltage 380-600V

J9

J8

J10

J13

Fault

Indication

N.O

S

3 Amp

Fuse