29 | Operation

Function

Description

Address

Details

Steam
output

The current steam output in Kg/Hr. or
LBS/hr See UNITS (Modbus 40031)

30105

Hex value representing the humidifies
steam output in kg/hr Resolution: 0.10
kg or LBS Example: 013B (hex) = 31.5
kg/hr or LBS/hr

Run hour
counter

The number of hours the humidifier has
been in operation since the last time the
run hour counter was reset

30106

Hex value representing the number of
humidifier operational hours since the
last reset. Resolution: 5 minutes
Maximum count: 5460 Hours. Example:
07D0 = 2000 hours

Humidifier
state

Describes the current state of the
humidifier and it’s I/O’s Contactor
ON/OFF Fill Valve ON/OFF Drain Valve
ON/OFF

30107

Bit Allocation Note More than one bit
can be active at any time. Contactor on
= 1 Fill valve on = 2 Drain valve on = 4

Alarms

The humidifier shall describe any faults
Too long to fill Excess Current End of
cylinder life No current

30108

Bit Allocation Note More than one bit
can be active at any time.
Too long to fill = 1
Excess current = 2
End of cylinder life = 4
No Current = 8

Maximum
production

The rated maximum steam production
for the humidifier

30111

Value written into Unit type (40205) is
also stored here

Firmware
version

The firmware version of the humidifier
controller

30113

Packed BCD version3.52 would be
0x0352