Nortec MES2 User Manual
Page 32
29 | Operation
Function
Description
Address
Details
Steam
output
The current steam output in Kg/Hr. or
LBS/hr See UNITS (Modbus 40031)
30105
Hex value representing the humidifies
steam output in kg/hr Resolution: 0.10
kg or LBS Example: 013B (hex) = 31.5
kg/hr or LBS/hr
Run hour
counter
The number of hours the humidifier has
been in operation since the last time the
run hour counter was reset
30106
Hex value representing the number of
humidifier operational hours since the
last reset. Resolution: 5 minutes
Maximum count: 5460 Hours. Example:
07D0 = 2000 hours
Humidifier
state
Describes the current state of the
humidifier and it’s I/O’s Contactor
ON/OFF Fill Valve ON/OFF Drain Valve
ON/OFF
30107
Bit Allocation Note More than one bit
can be active at any time. Contactor on
= 1 Fill valve on = 2 Drain valve on = 4
Alarms
The humidifier shall describe any faults
Too long to fill Excess Current End of
cylinder life No current
30108
Bit Allocation Note More than one bit
can be active at any time.
Too long to fill = 1
Excess current = 2
End of cylinder life = 4
No Current = 8
Maximum
production
The rated maximum steam production
for the humidifier
30111
Value written into Unit type (40205) is
also stored here
Firmware
version
The firmware version of the humidifier
controller
30113
Packed BCD version3.52 would be
0x0352