Steam lines and condensate returns – Nortec MES2 User Manual

Page 19

background image

Installation | 16

Steam Lines and Condensate Returns














Figure 12: Main Steam Line Requirements

Table 4: Recommended Steam Line Material

Steam Line

Material

Steam Line Length

ft m

Steam Line Description

Copper Tube

0-10

0-3

3/4 in MED-L Tubing (7/8 in. OD)

Stainless Steel

Tube

0-10 0-3

7/8 in. Tubing (0.049 W)

Nortec Hose

< 10

< 3

Part Number 1328810 (7/8”)

Note: Larger diameter lines should be used for steam runs longer than those listed. Contact Nortec for recommendation and

instructions on proper installation of reducers for larger diameter steam lines.

Table 5: Maximum Recommended Length of Steam Line

Steam Output

(Lb/hr)

Distance

(ft)

Possible Loss

(lb/hr)

Steam Line Size

(in)

5

8

1.0

3/4

10

15

1.5

3/4

1

15

20 2.0 3/4

1

20
25

25 2.5 3/4

1

30

NOTE: 1 Contact Nortec for information on possible losses of other steam line diameters used for longer runs.

2 The use of steam line other then copper, stainless steel tube or Nortec supplied steam line will void the

warranty and may adversely affect the operation of the humidifier

Steam Direction

Steam Direction

Steam D

irection

2 in.

(5 cm)

1 ft (30 cm)

1ft (30 cm)

0.5 in.

(12 mm)

10 Degrees

2 Degrees

Use Appropriate Slope

Insulate Pipe

1 in. (2.5 cm) pipe

insulation

MAIN RULES FOR ATMOSPHERIC STEAM LINES
 Slope the steam lines
 Trap condensate (Use full size ‘T’ for Traps)
 Condensate traps must be a minimum of 3 in. (15 cm) in height or duct static

pressure + 2 in. whichever is greater.

 Steam lines must not have any restrictions which could cause back pressure.
 1.0 in. (2.5 cm) pipe insulation recommended.
 Follow recommended materials, size and length see tables.