Operation | 28

Table 7: Modbus Addresses (Continued)

Function

Description

Address

Details

Force Drain When written to (FF), will interrupt the

humidification process and activate the
humidifier drain valve. After 20 minutes
the controller will reset this value (00).
After a microprocessor reset, the default
setting shall be (00)

40005

255 will start the process, 0 will be
accepted, to clear if the request has not
been cleared itself

Reset Run
Hour
Counter

Resets the humidifier controller’s run
hour counter to zero hours

40006

255 will start the run hours counter
process. 0 will be accepted to clear the
run hours counter.

Set Modbus
address

Change the humidifier controller’s
MODBUS address. Range is 1-247. This
setting shall be non-volatile with a
default setting of 1.

40201

The value changes will only take effect
following a hardware reset of the control
board.

Set Modbus
Baud rate

Changes the humidifier’s baud rate.
Range is 4800, 9600, and 19200 B/sec.
This setting shall be non-volatile with a
default value of 9600 B/sec.

40202

The value changes will only take effect
following a hardware reset of the control
board

Set Modbus
parity

Change the humidifier controller’s
MODBUS parity. Range is None, Even,
Odd This setting shall be non-volatile with
a default setting of Even.

40203

The value changes will only take effect
following a hardware reset of the control
board

Units

Required by the control board for
capacity calculations

40204 0=LBS,

1=KG

Unit type

Required by the control board for current
and capacity calculations

40205

Depending on the setting in UNITS
(Modbus: 40204) Hex value
representing maximum unit capacity
(100% fill off amps)

Unit voltage

Required by the control board for
current and capacity calculations

40206

Hex Value Unit Type
0 110-120
1 208
2 220-240
3 230
4 277
5 347
6 380
7 400
8 415
9 440-480
A 550-600

Unit phase

Required by the control board for current
and capacity calculations

40207 Bit

Allocation

Single phase = 1
Three phase = 2
Three phase (6 electrode) = 4

Electrode
current

The value of the electrode current in
Amps

30104

Hex value representing the humidifies
current in amps Resolution: 0.10 amps
Example: 015F (hex) = 35.1 Amps