beautypg.com

Extended shutdown – Nortec MES2 User Manual

Page 39

background image

Maintenance and Servicing | 36

Extended Shutdown

Should it be required to disconnect power to the humidifier for a period of extended shut-down,
always drain the cylinder first. Otherwise, the electrodes are subject to harmful corrosion which
drastically shortens the cylinder life.
1 Switch the On/Off/Drain Switch to the Drain position.
2 Wait until the humidifier is completely drained (usually takes less than 10 minutes).
3 Turn the On/Off /Drain switch to the off position.
4 Shut off power to the humidifier with the external disconnect.
5 Close the supply water shut-off valve.

Starting After Extended Shutdown

1 Check to see the humidifier has not been damaged and the installation has not been

altered.

2 Open the supply water shut-off valve.
3 Turn on the power to the humidifier with the external disconnect.
4 Turn the On/Off/ Drain switch to the On position.
5 Follow the start up procedure in the section titled Start Up Procedure on page 30.

Note: As long as the MES2 is powered, it will automatically drain the cylinder when there

has not been a call for humidity for an extended period of time. This feature will reduce or

prevent the possibility of corrosion of the electrodes and the accumulation of algae and

bacteria growing in the cylinder. The cylinder will remain empty until there is a call for

humidity at which time the fill valve will open and refill the cylinder. The unit will go

through its normal process for optimum operation.

Caution:
 Do not leave the switch in the DRAIN position indefinitely as the drain coil could burn

out.

 When disconnecting power to the humidifier for an extended period of time drain the

cylinder first to prevent harmful corrosion.