19 | Installation

Primary Voltage Wiring

































Figure 17: Primary Power Connection

L2

L1

3 Phase

Note:
1

2

3

4

5

6

Ensure mains voltage and HWS

jumper settings match operating
voltage (see table below for setting,
see Figure 21 for jumper location).

Dedicated fused disconnect
must be installed. Fusing must
not exceed max circuit protection
as indicated on the specification
label.

Ensure that adequate power

is available to carry full
humidifier amp draw as
indicated on the specification
label.

Insert wires into cylinder plugs

and tighten with 2mm allen wrench
to11 in-lb.

Ensure both plumbing cabinet

and remote electrical bracket

(if present) are grounded. Use
ground wires if required.

All wiring to be in accordance

with national and local
electrical codes.

1 Phase

L3
L2

L1

Disconnect

Contactor

Disconnect

Contactor

Cylinder
plug with

white
marker

Current

transformer

Current

transformer

Cylinder
plug with

white
marker

Secure wires with tie

wraps to tabs provided

in mounting bracket

Cylinder Plugs

Mains Voltage

Jumper

HWS Jumper

600

480

380

277

240

208

Mains Voltage and HWS Select

J1
J2
J3
J4
J5
J6

J8

J9

Ground Lug

(on cabinet ATT or

on bracket REM)

Cabinet ground wire

Remote Electrical Bracket

ground wire