Typical mes2 installation – Nortec MES2 User Manual
Page 15
Installation | 12
Typical MES2 Installation
* Dimensions and brackets are recommendations based on best practice. OEM must verify operation if they are not followed or used.
Figure 8: Typical Humidifier Installation
Control
Wiring
Pg 20
Plumbing
Pg 15
Primary
Voltage
Pg 19
1 ft (30 cm)
min. before
any bend*
12 in. (30 cm)
min. radius*
Condensate
trap
2 in. (5 cm)
min.
1 ft (30 cm)
Support
brackets*
Fuse
O
n
/O
ff
(
S
a
f
e
t
y
L
oo
p
)
2
4
V
A
C
On/Off
Drain
Switch
2
4
V
A
C
C
o
n
t
a
c
t
o
r
E
n
er
gi
ze
Power Relay
L2
L1
Disconnect
Contactor
Current transformer
Cylinder
plug with
white
marker
Note:
Single Phase
Connection Shown
0.875 in.
(22 mm).
OD
1/8 in.
NPT
Air gap
recom-
mended
Drain
7/8 in. Min.
Cold Potable Water
30 - 80 PSIG
Front side
clearance required
for cylinder removal.
36 in. (90 cm)
recommended
r
Fill
Line
Drain
Line
Steam Line
Steam
Distribution
Location
Mounting
Pg 13