13 | Installation

Location

Mount to structural member or on surface capable of supporting the humidifier’s operating
weight (see Figure 4: MES2 Dimensions and Weights). The humidifier may be set on its base but
clearance must be provided for the drain line to be sloped adequately. In general clearance is
not required around the humidifier except for maintenance access and electrical and plumbing
connections.
 The clearance dimensions shown are recommendations based on best practice. OEM must

verify operation if they are not followed.

 Install only in areas with ambient temperature 41-104°F (5–40°C) relative humidity 5 -

95%.

 When possible install below the steam distributor. If mounted above the steam distributor

take care to provide proper steam line routing and proper condensate traps.

 DO NOT locate the humidifier any further then absolutely necessary from the steam

distributor location as net output will be reduced as a result of heat loss through the steam
line.

 The main service access required is for changing the cylinder. This access can be from the

front or right side. Right side service access is not possible with the optional plumbing
enclosure.




* Dimensions are recommendations based on best practice. OEM must verify operation if they are not followed.

Figure 9: Mounting Location / Clearance

Note: Nortec recommends a vertical drop from the drain outlet and an air gap as close

as possible to the drain outlet to insure proper draining of the humidifier.

36 in. (92 cm)*

side clearance

for right side

cylinder removal

only.

36

*

front clearance

for front cylinder

removal and/or for

attached electronics

models only.

in. (92 cm)

Mount level

As close as

possible to steam

distributor

5-95%

0.5 in. (1.3 cm)*

top clearance

access hole required

for steam outlet and

optional condensate

return to fill cup.

8 in. (20 cm)*

left side clearance

for removal of cover

on attached closed
electronics models

only.

0 in. (0 cm)

front clearance

for right side

cylinder removal

0

0

side clearance

for front cylinder

removal

in. ( cm)

Note:

side cylinder

removal not

possible with
enclosed
pluming option.

0 in. (0 cm)

access hole or

additional clearance

required for fill

connection

0 in (0 cm) bottom clearance.

Access for properly sloped drain required.

0.2 (0.5 cm)*

for fill cup

tabs.