Installation | 22

MES2 Installation Checklist

Unit Serial #: _________________ No. of humidifiers: _______ Tag: _______________
Unit type: _______ __________

Voltage: ________V/_____ph

Cylinder type:

Customer/Job:

Address:

WATER QUALITY:

Well

water

City water 

POWER:

 Voltage, amp, fuse per Spec Label:

yes  no 

 Jumper 1-6 setting _________________

 Jumper 8/9 settting ________________
 Disconnect switch

yes  no 

HUMIDIFIER MOUNTING: (Clearances around the unit Acceptable Obstruction)

 Humidifier level. 

Cylinder removal clearance 

STEAM LINE(S):

 Material

Diameter / Size 

 Slope up (min 2 in/ft). 

Slope down (min 0.5 in/ft) 

 Low point condensate traps 

No hose kinks / Restrictions 

 Type of Insulation if installed

CONDENSATE LINE(S):

 P Trap min 6 in or duct press + 2 in 

P Trap sufficient drop to ensure flow 

WATER LINE:

 1/2 in to within 4ft of unit 

Water pressure: 30-80 psig 

DRAIN LINE:

 Diameter / Size ______________ Air gap within 3 ft of the unit 

CYLINDER:

 Seated in drain valve and secured

yes  no 

WIRING:

 Wiring connections and connectors secured

yes  no 

CONTROLS:

 On / Off / Security loop devices working correctly yes  no 

 Jumper J10 set to
Modulating (removed) 

Or
On/Off (installed) 
 Jumper J26 set to

Terminal block input control (removed) 

Or
Modbus control (installed) 


Inspected by:

Date of inspection: ______/_______/______


Company: