Installation | 20

Control Wiring

































Figure 18: Control Wiring

24 VAC

On/Off
Safety Loop

Control
Signal

Cut-out

in cover

for wiring

Contactor

Tie wrap

wires to tabs

provided

Electrical Cover

(Enclosed electrical

models only)

Remote Fault

(NO)

Control (+)

Signal (-)

On/Off (Safety Loop) 24VAC

On/Off

Drain

Switch

24 VAC

P2

P5

P3

Fuse+Power Relay

Contactor

Mandatory Wiring:

1
,
2

3
Optional Wiring:
4

5

6

Use min. 18 AWG and keep as short as possible.

24 VAC to fuse connected to On/Off/Drain switch

and to power relay 0.25 in. spade connectors.

Ground wire from humidifier ground to air handler

ground.

On/Off/Safety input (24 VAC) input to point 2 of P3.

Modulating control input (0-10 or 2-10 VDC)to P5
(J10 must be removed for modulation).

500 ohm resistor between 1-2 of P5 for mA

modulating control input.

Remote Fault to P2.

Power Relay

Fuse

Contactor
Ground