Required maintenance, Cylinder spent fault, Replacement cylinder – Nortec MES2 User Manual
Page 35
Maintenance and Servicing | 32
Required Maintenance
The MES2 humidifier has been designed to require very little maintenance. Regular
maintenance consists of checking the humidifier to insure it is in good condition, replacing the
cylinder when the software advises that the cylinder is spent and cleaning out the drain valve
whenever the cylinder is replaced.
Cylinder Spent Fault
When the cylinder is spent the MES2 will stop operating and the yellow LED will flash in a
repeating pattern of 4 flashes. At this time the cylinder must be replaced. See Table 7:
Troubleshooting MES2 Faults on page 43 for more information on other flash sequences.
The steam cylinder is disposable and must be replaced at end of cylinder life. Cylinder life is
dependent on water supply conditions and humidifier usage.
Replacement Cylinder
The label on the existing cylinder identifies the cylinder type in its top left corner. When ordering
a cylinder always quote the three or five digit model number on the label, the humidifier’s serial
number, and the humidifiers voltage. Serial number and voltage are located on the
specification label on the left side of the humidifier.
Figure 23: MES2 Cylinder
Note: Nortec recommends keeping a replacement cylinder in stock throughout the
humidification season. This will prevent possible downtime when the humidifier reports
cylinder end of life.
Caution: Failure to replace the cylinder at the end of cylinder life will result in improper
operation and may result in damage to the humidifier. Nortec is not responsible for any
damages resulting from, or attributed to, the failure to replace a spent cylinder (see
Manufacturer’s Warranty).
Electrode Pin
Connect color coded cylinder
plugs to pin with corresponding
color label. There may be 2 or 3
connections depending on
cylinder.
The spring loaded plug should
fit snugly on the pin. Replace if
loose or any signs of damage.
Steam Outlet
Secure steam hose to
outlet with hose clamp.
High Water Sensor Pin
Has a plastic collar
around it.
Connect
orange high water
sensor wire here.
Label
Identifies cylinder type in
top left. Always replace
cylinder with the same
model.