33 | Maintenance and Servicing

Removing the Cylinder

1 Drain the existing cylinder by switching the On/Off/Drain switch to the Drain position. Let

the humidifier drain until no more water is flowing out to drain (usually not more than 10
minutes).

2 Turn the humidifier On/Off/Drain switch to off.
3 Close supply water shut off valve.
4 Turn off power to the humidifier with the external disconnect.
5 If enclosed plumbing option is installed remove the screw securing the front cover.
6 Remove the cylinder plugs from the cylinder pins by pulling vertically.
7 Using a flat screwdriver loosen the hose clamp where the hose is connected to the cylinder.
8 Using a small flat screwdriver press the tab on the cable tie holding the cylinder in place and

pull the cable tie open.

9 Tip the top of the cylinder forward to pivot it out of the steam hose. When free of steam

hose lift the cylinder out.



















Figure 24: Cylinder Removal

Warning
 Check to see if yellow service LED is flashing (see Figure 20: User Interface on

page 24) then disconnect main power at the external disconnect before any

servicing.

 The inside of the humidifier’s cabinet contains high voltage components and

wiring. Access should be limited to authorized personnel.

Hose Clamp

Cylinder Plug

lift vertically

On/Off/Drain Switch

Tilt cylinder

forward to clear

hose and then

lift from drain

valve.

Cable Tie