43 | Troubleshooting

MES2 Faults

The self-diagnostic system built into the MES2 is continually monitoring the operation of the
humidifier. When an abnormal condition occurs that cannot be self corrected by the software
the MES2 will turn off power to the cylinder, drain the cylinder, and annunciate the fault using
the yellow status LED.

LED Flash Sequence

To differentiate between different fault conditions the yellow LED is flashed in different
sequences. Table 7 lists MES2 faults, their meaning, possible causes, and corrective actions.

Clearing a Fault

 Check the flash sequence against the list of fault messages and take any necessary actions

to correct the cause(s) as outlined in Table 7: Troubleshooting MES2 Faults.

 Power cycle the humidifier with the On/Off switch. Wait 3 seconds between off and on.

Table 7: Troubleshooting MES2 Faults

Yellow LED

System Detected

Cause

Corrective Action(s)

1 flash

Excess Current
Current has exceeded

130% of max

1 Drain blocked water over

concentrated

1 Clean the drain line and drain

valve.

2 Drain solenoid not energized,

water over concentrated

2 Check and correct wiring to

drain valve.

3 Filling too fast, fill valve

damaged

3 Check fill rate and replace the

fill valve if needed.

4 Water supply too conductive

4a Contact Nortec

representative for

recommendation on alternate

cylinder

4b Change the water supply

5 Humidifier short cycling

5a Check if high limit or other

On/Off control is cycling

On/Off in less than 5

minutes. Check location and

setting of high limit.

5b Reduce the output by

turning down the capacity

potentiometer.

5c If modulating control check

if controller Pband too tight.

5d Check for temperature

swings.

6 Wrong cylinder installed

6 Install correct cylinder model

7 Cylinder Spent but not

detected by software

7 Replace the cylinder (see

maintenance chapter)

8 Condensate from other

source

8 Remove condensate returns

other than from steam line.

9 Back pressure

9 Eliminate back pressure