beautypg.com

4 evaporator fan assembly, 5 wiring notice, 6 perform the inspection – MovinCool Classic 40 Service Manual User Manual

Page 73: Evaporator fan assembly, Wiring notice, Perform the inspection

background image

Repair Section

73

9.4 Evaporator Fan Assembly

Install evaporator fan. Allow a clearance of 0.06

in (1.5 mm) or more on side of the evaporator fan.

CAUTION

• Tightening torque:

- 13.3 ± 0.6 ft•lbf (18.0 ± 0.8 N•m)

9.5 Wiring Notice

• Secure the wires using clamps so that they do not come into contact with the edges of the

structure, etc. Secure the wires using clamps in the same position they were before removal.

9.6 Perform the Inspection

• Perform the inspection of cooling performance and check for abnormal noise or abnormal

vibration.

I002649

0.06 in
(1.5 mm)
or more

0.06 in
(1.5 mm)
or more

This manual is related to the following products: