Operation Section

42

5.16 Temperature Thermistor

• The room thermistor (RTS) is installed

upstream of the evaporator, and detects

evaporator inlet temperature as a resistance

value.

• The freeze protection thermistor (CTS) is

installed in the evaporator outlet piping, and

detects low temperature on the evaporator as

a resistance value.

Type

Specification

Characteristic

“Short” Detection

“Open” Detection

Room Thermistor (RTS)

5 k ohm at 77 °F (25 °C)

0.3 k ohm or less at 181 °F

(83 °C) or more

180 k ohm or more at -29 °F

(-34 °C) or less

Freeze Protection

Thermistor (CTS)

5 k ohm at 77 °F (25 °C)

0.3 k ohm or less at 181 °F

(83 °C) or more

180 k ohm or more at -29 °F

(-34 °C) or less

I001695

This manual is related to the following products: