6.8 Wiring Connection Inspection

• While referring to the wiring diagrams, check the connection of each wire.

CAUTION

Secure the wires using clamps to prevent contact with the edges of the structure, etc. Secure the

wires in the same position as prior to removal.

6.9 Refrigerant System Inspection

• In most cases, the probable cause for insufficient cooling is a clogged system, leakage or an

incorrect amount of refrigerant. In such cases, inspect the system according to the following

procedure.

(1) Inspection of clogged system

• Check the component parts of the refrigerant system, including piping, that could be clogged

with refrigerant. If clogged with refrigerant, only the clogged part is frosted partially. In such a

case, change the part in question.

(2) Inspection of refrigerant leak

• Carefully check all connections, and each component for leaks whenever the refrigerant system

is installed or repaired. Use an electronic gas leak tester to inspect the system.

(3) Insufficient refrigerant

• In case the unit is judged to be deficient in cooling capacity, make sure to perform the inspections

(1) and (2) described in “Repair of Refrigerant System” on page 62 to confirm the cause of

trouble. Then, charge the system with refrigerant to the specified amount.