Operation Section

29

5.5 Warning Signal Connection (Output Signal Terminal L+ and L-)

• The controller is equipped with a warning signal output relay type (Form C, normal open dry

contact) which can be used to monitor the failure condition.

• Relay contactor is closed when the unit operates abnormally.

• The relay output contactor is rated 2 A at 30 VDC or 2 A at 30 VAC (resistive load) and it is

compatible with various warning devices such as alarm speaker, light indicators, etc.

< NOTE >

Use recommended warning signal wire size from 16 AWG to 26 AWG for a solid wire, or 16 AWG

to 22 AWG for a stranded wire with ring terminal for #6 stud size.

• Connect the warning device to terminal L+ and

L- according to its polarities.

I003205

Unit Terminal

Warning Device

Open Dry Contact

Relay Output Contactor

(DC12 V, 0.01 A - 0.02 A)

E+
E-
L+
L-