beautypg.com

6 removal of electrical components, Removal of electrical components – MovinCool Classic 40 Service Manual User Manual

Page 61

background image

Repair Section

61

7.6 Removal of Electrical Components

(1) Control box

1) Take out the four (4) bolts, and then remove the front panel. (See “Disassembly” on page 55.)

2) Take out the three (3) screws, and then open the control box cover. (See “Disassembly” on page 55.)

3) Disconnect each connector, and then remove the electrical parts from the control box.

4) Remove electrical parts.

- Compressor motor relay: Remove two (2) screws and two (2) washers from the holder.

- Fan motor relay: Remove the fan motor relay from the holder.

- Reverse phase protector: Remove four (4) supports from the control box.

- Over current relay 1: Remove two (2) screws and two (2) washers from the control box.

- Over current relay 2: Remove two (2) screws and two (2) washers from the control box.

- Terminal block 1: Remove two (2) screws from the control box.

- Terminal block 2: Remove two (2) screws from the control box.

- Terminal block 3: Remove two (2) screws from the control box.

- Relay board fuse: Take out the fuse from the relay board.

- Relay board: Remove six (6) supports from the control box.

I003100

T

RS

E+
E-

L+
L-

RC

Y
G

Terminal Block 2
(for Signal Connection)

Terminal Block 3
(for Signal Connection)

Relay Board

Relay Board Fuse

Compressor Motor Relay
(for Compressor and Condenser Fan Motor)

Reverse Phase Protector

Terminal Block 1
(for Power Cord)

Fan Motor Relay
(for Evaporator Fan Motor)

Overcurrent Relay 2
(for Condenser Fan Motor)

Overcurrent Relay 1
(for Evaporator Fan Motor)

This manual is related to the following products: