beautypg.com

6 high pressure switch, High pressure switch – MovinCool Classic 40 Service Manual User Manual

Page 21

background image

Operation Section

21

4.6 High Pressure Switch

• The high pressure switch prevents the

condenser and compressor from being

damaged by excessively high pressure in the

high pressure line of the refrigeration cycle.

The switch is normally closed. The snap disk

responds to the variations in pressure and, if

pressure is abnormally high, the snap disk

moves down to push the pin down, causing the

internal contacts to open. This interrupts the

ground signal at the control board (CN13 connector) which turns the compressor off.

• Possible causes of this trouble include:

- The condenser air filter is dirty, restricting air flow.

- The condenser blower is defective.

I001768

Pressure of Refrigerant

Movable Point

Snap Disk

Pin

Terminal

Lead Wires

Stationary Point

Molding by Resin

Case

This manual is related to the following products: