MovinCool Classic 40 Service Manual User Manual
Page 30

Operation Section
30
5.6 Fire Alarm Control Panel Connection (Input Signal Terminal E+ and E-)
• The controller is equipped with a normal open input signal connection, which can be connected
directly from the fire alarm control panel. This input signal terminal should only be connected to
a close or open dry contact signal. When receiving the signal from the fire alarm control panel,
the unit turns off and does not turn back on until it has been RESET.
< NOTE >
Use recommended fire alarm signal wire size from 16 AWG to 26 AWG for a solid wire, or 16 AWG
to 22 AWG for a stranded wire with ring terminal for #6 stud size.
• Connect the fire alarm device to terminal E+
and E- according to its polarities.
I003206
Unit Terminal
Output Signal
Fire Alarm Device
Open Dry Contact:
2 A at 30 VDC or 2 A at 30 VAC
(resistive load)
E+
E-
L+
L-