Operation Section

34

(2) Input signal

• The relay board receives inputs from the control panel, sensors, and external devices to perform

device control.

Control Panel Input

Sensor Input

External Input Signal Specification

Symbol

Indication

Function

Connector

SW1

ON/OFF Button

On/off control for unit operation. Turns the unit on and off.

CN17

SW2

FAN Button

Changes the fan control mode between continuous and automatic

on/off control.

SW3

SET TEMP

Button

Increases the set temperature.

SW4

SET TEMP

Button

Decreases the set temperature.

Symbol

Type

Specification

Connector

Characteristic

“Short” Detection

“Open” Detection

RTS

Room Thermistor

5 k ohm at 77 °F

(25 °C)

181 °F (83 °C) or

more

-29 °F (-34 °C) or

less

CN11

CTS

Freeze Protection

Thermistor

5 k ohm at 77 °F

(25 °C)

181 °F (83 °C) or

more

-29 °F (-34 °C) or

less

CN12

Symbol

Signal

Specification

Function

Connector

E+, E-

Fire Alarm Input

On: Between 10 to 20

mA at DC12 V

(Off: No signal)

On: Activates “Defect control”

(Contact: Normally open)

LED shows “AL”, Output signal “ON”

On board buzzer sound

CN15

OCF1,

OCF2

Thermal Relay

Protection

On: Between 10 to 20

mA at DC12 V

(Off: No signal)

Off: Activates “Defect control”

(Contact: Normally closed)

LED shows “FL”, Output signal “ON”

CN16

HPRS

High Pressure

Switch

On: Between 0.5 to 1.0

mA at DC5 V

(Off: No signal)

Off:

1) < 120 sec.: Compressor stops.

2) 120 sec.<: Compressor stops.

LED shows “HP” output signal “ON”

CN13