Repair Section

50

(3) Inspection of cooling capacity performance

• Measure the difference in temperature between the inlet of the evaporator and the cool air vent.

If the difference is out of the range given in the graphs on page 14, proceed with the remedy

suggested in the troubleshooting chart on page 45 to 49.

I003097

Cool Air Out

Evaporator Air In

Thermometer

Thermometer