Repair Section

48

Condition

Possible Cause

Remedy

Checking Area

Cause

Stops

immediately

after

starting

Control

panel

display

normally.

1. Fan on-off relay on the relay

board.

Open circuit or insufficient

contact.

Replace relay board.

2. Compressor motor relay.

Open circuit or insufficient

contact.

Replace compressor

motor relay.

3. Compressor relay on the

relay board.

Open circuit or insufficient

contact.

Replace relay board.

4. Reverse phase protector.

Open circuit or insufficient

contact.

Replace reverse phase

protector.

Stops after

running a

while

Control

panel

display

normally.

1. Resistance of compressor.

Operation of safety device

(IOLC) due to compressor

malfunction.

See “Inspection of

Compressor Motor” on

page 52.

2. Refrigerant leakage.

Insufficient refrigerant or gas

leakage.

Repair and charge

refrigerant.

3. Dirt on evaporator or

condenser.

Insufficient cooling of

evaporator or condenser.

Clean evaporator or

condenser.

4. Duct connection condition.

Leak or clogged by improper

duct connection.

Repair duct connection.

5. Duct length and diameter

Too long or too small

diameter of duct.

Fix duct.