beautypg.com

MovinCool Classic 40 Service Manual User Manual

Page 32

background image

Operation Section

32

(2) Fan only mode

• When the FAN button on the control panel is pressed, the FAN “ON” LED illuminates, and the

fan operates. At this time, the compressor is off, and only the fan is in operation. When the FAN

button is pressed again, the fan stops.

(3) Cool mode

• When the COOL ON/OFF button is pressed, the FAN “ON” LED illuminates, and room

temperature is shown on the display. At this time, the compressor and fan begin to operate to

provide cooling. When the COOL ON/OFF button is pressed again, the compressor and fan

stop.

• When the COOL ON/OFF button is pressed in fan only mode, room temperature is shown on

the display, and the compressor operates to provide cooling. If room temperature reaches the

set temperature during cooling operations, the compressor stops, and only the fan continues to

operate. (Fan operate mode: * Initial setting)

< NOTE >

The fan only mode will not operate after the cool mode has been activated. Once the cool mode

is activated, the unit cannot be turned off by pressing the fan button. Rather, the COOL ON/OFF

button must be pressed.

*Fan stop mode

- In fan stop mode, if room temperature reaches the set temperature during cooling operations,

both the compressor and fan stop. The fan stop mode setting can be changed using the dip

switch on the relay board. (For details, see “Dip switch setting” on page 35). During cooling

operations when in the fan stop mode, the FAN “AUTO” LED illuminates.

(4) Change temperature mode “°C” and “°F”

• The temperature display can be switched between “°C” and “°F” by holding down the SET TEMP

buttons (

, ) and the FAN button simultaneously for at least three sec.

(5) Diagnostic code

• Most of the diagnostic codes can be RESET by holding down the SET TEMP buttons (

, )

simultaneously for at least 3 sec. (For details, see “Self-Diagnostic Codes” on Page 44.)

This manual is related to the following products: