beautypg.com

4 removal of condenser fan assembly, Removal of condenser fan assembly – MovinCool Classic 40 Service Manual User Manual

Page 57

background image

Repair Section

57

7.4 Removal of Condenser Fan Assembly

1) Take out the two (2) screws, and then remove the

sub-control box cover.

2) Disconnect the three (3) power supply wires from

the terminal, and disconnect the ground wire.

3) Take off the nut (left-handed screw) and two (2)

washers, and then remove the condenser fan.

CAUTION

• Tightening torque (for Installation):

- 32.5 ± 3.6 ft•lbf (44.1 ± 4.9 N•m)

4) Take off the four (4) nuts, and then remove the

condenser fan motor.

I002637

Screws (2)

Sub-Control Box Cover

I002638

Power Supply Wires (3)

Terminal

Ground Wire

I002639

Fan

Nut (1)
(Left-Handed Screw)

Washers (2)

I002640

Nuts (4)

Motor Stay

Fan Motor