6.5 Inspection of Fan Motor
• Measure resistance across the terminals of the
fan motor (except the ground terminal). (All
terminals must be disconnected from the unit.)
- Condenser fan motor: Approx. 16.2 ohm (at
68 °F (20 °C))
- Evaporator fan motor: Approx. 5.93 ohm (at
68 °F (20 °C))
• If the measured resistance is not equal to the
standard values listed above, replace the fan
motor.