3 fan assembly, 4 wiring notice – MovinCool Classic 10 Service Manual User Manual
Page 72

Repair Section
72
11.3 Fan Assembly
• Install the evaporator fan and condenser fan.
more between the evaporator fan and the fan
casing.
CAUTION
• Tightening torque:
- 10.69 ± 1.04 ft•lbf (14.5 ± 1.4 N•m)
11.4 Wiring Notice
• Secure the wires using clamps so that they do not come into contact with the edges of the
structure, etc. Secure the wires using clamps in the same position they were before removal.
I002608
0.06 in
(1.5 mm)
or more
0.06 in
(1.5 mm)
or more
Allow a clearance of 0.06 inch (1.5 mm) or
5) Apply insulators to the accumulator and pipe 2.
Pipe 2
Insulator
Accumulator
ILL00602-00
< NOTE >
Insulators are packaged in the supplied
compressor assembly.
This manual is related to the following products: