Repair Section

43

8.5 Compressor Inspection

(1) Compressor motor inspection

• Measure resistance across the terminals of the

compressor motor.

• If the measured resistance is not equal to the

standard values listed above, replace the compressor. The compressor has an external

overload relay. The overload relay should be operational if the above resistance is obtained

under normal temperature. For overload relay specifications, refer to the chart below.

(2) Overload relay inspection

• Check for continuity across two terminals of the

overload relay. At normal temperature, there

should be continuity across the terminals.

• If there is no continuity across the terminals,

replace the overload relay.

Resistance at 77 °F (25 °C)

R-C

C-S

Approx. 0.83 ohm

Approx. 1.92 ohm

Operating Temperature

OFF (open contacts)

ON (closed contacts)

302 °F (150 °C)

142 °F (61 °C)

ILL00603-00

I001701

8.6 Fan Motor Inspection

• Measure resistance across the terminals of the

fan motor.

• If the measured resistance is not equal to the

standard values listed above, replace the fan

motor.

Resistance at 68 °F (20 °C)

CF1-TBT

CF2-TBT

Approx. 7.06 ohm

Approx. 8.73 ohm

I001702

TBT

CF2

CF1