3) input signal – MovinCool Classic 10 Service Manual User Manual
Page 22

Operation Section
22
3) Input signal
• The relay board receives inputs from the control panel, sensors, and external devices to perform
device control.
Control Panel Input
Sensor Input
External Input Signal Specification
Symbol
Indication
Function
Connector
SW1
ON/OFF Button
On/off control for unit operation. Turns the unit on and off.
CN17
SW2
FAN Button
Changes the fan control mode between continuous and automatic
on/off control.
SW3
SET TEMP
Button
Increases the set temperature.
SW4
SET TEMP
Button
Decreases the set temperature.
Symbol
Type
Specification
Connector
Characteristic
“Short” Detection
“Open” Detection
RTS
Room Thermistor
5 k ohm at 77 °F
(25 °C)
181 °F (83 °C) or
more
-29 °F (-34 °C) or
less
CN11
CTS
Freeze Protection
Thermistor
5 k ohm at 77 °F
(25 °C)
181 °F (83 °C) or
more
-29 °F (-34 °C) or
less
CN12
Symbol
Signal
Specification
Function
Connector
AUX2
Fire
Alarm
Input
On: Between 10 to 20
mA at DC12 V
(Off: No signal)
On: Activates “Defect control”
(Contact: Normally open)
LED shows “AL”, Output signal “ON”
On board buzzer sound
CN15
TANK
FULL S/W
Tank Full
Switch
On: Between 10 to 20
mA at DC12 V
(Off: No signal)
Off: Activates “Defect control”
(Contact: Normally closed)
LED shows “FL”, Output signal “ON”
CN16
AUX1
External
Pump
Failure
On: Between 10 to 20
mA at DC12 V
(Off: No signal)
Off:
1) From 1 to 180 seconds - Compressor stops.
2) After 180 seconds - Compressor stops.
LED shows “AS”, Output signal turns “ON”
CN13
High
Pressure
Switch
On: Between 0.4 to 1.0
mA at DC 5V
(Off: No signal)
Off: Activates “Defect control”
(Contact: Normally closed)
1) Activates 3 times in 24 hours:
LED shows blinking “HP”.
2) Activates 10 times in 24 hours:
LED shows “HP”, Output signal “ON”
CN03
HPRS
*1
*1 : For unit serial number from November 2011 (1111) to Present