4 refrigerant charging work, 5) evacuation (repeat), Caution – MovinCool Classic 10 Service Manual User Manual
Page 69: 1) refrigerant charging

Repair Section
69
(5) Evacuation (repeat)
1) Close the valve of the refrigerant cylinder. Then
remove the charging hose (green) from the
refrigerant cylinder, and connect it to the
refrigerant recovery machine.
< NOTE >
Keep the high pressure valve and the low
pressure valve of the gauge manifold closed.
2) Using the procedure under “Evacuation”, evacuate
the system until the high pressure gauge indicates
30 inHg (100 kPa) or higher. (For 15 minutes or more.)
3) After evacuation is complete, close the high and
the low pressure valves of the gauge manifold.
CAUTION
Make sure to evacuate the system twice or
more using the repetitive vacuum method.
Evacuate the system an additional time on
rainy or humid days.
10.4 Refrigerant Charging Work
(1) Refrigerant charging
4) Remove the charging hose (green) from the
vacuum pump, and connect it to the refrigerant
cylinder (R-410A).
5) Loosen the nut on the gauge manifold side of the
charging hose (green). Open the valve of the
charging hose (green). Open the valve of the
refrigerant cylinder. After air purging, tighten the
nut and close the valve of the refrigerant cylinder.
I002227
LO
Closed
HI
Open
LO
Closed
HI
Closed
Valve Setting
30 inHg (100 kPa) or larger
High Pressure Valve
High Pressure Gauge
Gauge
High Pressure
Side Tube
Vacuum Pump
(in Operation)
Low Pressure
Valve
I001901
Open The Valve
of Refrigerant
Cylinder
To Process Tube Fitting
Charging Hose
(Green)
Refrigerant
Cylinder R-410A
Red
LO
Closed
HI
Closed
Valve Setting
Air Purging