background image

Repair Section

69

(5) Evacuation (repeat)

1) Close the valve of the refrigerant cylinder. Then

remove the charging hose (green) from the

refrigerant cylinder, and connect it to the

refrigerant recovery machine.

< NOTE >

Keep the high pressure valve and the low

pressure valve of the gauge manifold closed.

2) Using the procedure under “Evacuation”, evacuate

the system until the high pressure gauge indicates

30 inHg (100 kPa) or higher. (For 15 minutes or more.)

3) After evacuation is complete, close the high and

the low pressure valves of the gauge manifold.

CAUTION

Make sure to evacuate the system twice or

more using the repetitive vacuum method.

Evacuate the system an additional time on

rainy or humid days.

10.4 Refrigerant Charging Work

(1) Refrigerant charging

4) Remove the charging hose (green) from the

vacuum pump, and connect it to the refrigerant

cylinder (R-410A).

5) Loosen the nut on the gauge manifold side of the

charging hose (green). Open the valve of the

charging hose (green). Open the valve of the

refrigerant cylinder. After air purging, tighten the

nut and close the valve of the refrigerant cylinder.

I002227

LO

Closed

HI

Open

LO

Closed

HI

Closed

Valve Setting

30 inHg (100 kPa) or larger

High Pressure Valve

High Pressure Gauge

Gauge

High Pressure
Side Tube

Vacuum Pump
(in Operation)

Low Pressure
Valve

I001901

Open The Valve
of Refrigerant
Cylinder

To Process Tube Fitting

Charging Hose
(Green)

Refrigerant

Cylinder R-410A

Red

LO

Closed

HI

Closed

Valve Setting

Air Purging