Repair Section

36

Indication

Condition

Output

Signal

Buzzer

(On Board)

No. 3*

1

When the high pressure switch (connected to

If the high pressure switch is activated 3 times in

CN03) is activated (= CN03 input turns open) for

the first 2 times in 24 hours, “HP” turns on but

24 hours, “HP” blinks and signal output (CN24)
turns on.

goes away as the high pressure switch resets.

No

No

Yes

No

When the high pressure switch is activated 10

times in 24 hours, “HP” turns on and signal

output (CN24) turns on.

Yes

No

(

/

) simultaneously for 3 seconds, and the

controller returns to normal status.

No. 4

Improper hose connection (including kink or

blockage) or a defect in the condensate pump

for more than 180 seconds will display "AS" on

the LED resulting the compressor to stop

immediately; however, fan will continue to

operate.

Normal condition is resumed when condensate

pump or hose connection is fixed, and the unit

has been RESET.

Yes

No

To RESET, hold down the SET TEMP buttons

To RESET, hold down the SET TEMP buttons

(

/

) simultaneously for 3 seconds, and the

controller returns to normal status.

No. 5

When room thermistor becomes open or

shorted, display shows “E1” and cool mode

operation is off. Display and cool mode

operation are returned to normal operation after

condition is corrected.

Yes

No

No. 6

When freeze protection thermistor becomes

*1 : For unit serial number from November 2011 (1111) to Present

open or shorted, display shows “E2” and cool

mode operation is off. Display and cool mode

operation are returned to normal operation after

condition is corrected.

Yes

No