Repair Section
63
10.2 Removal of Refrigeration System Components
CAUTION
• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal/min (1 L/min))
through the pinch-off tube during any brazing operation.
• During any component replacement involving brazing, shield nearby parts with a steel plate
to protect them from the flame.
ILL00579-00
Part to Replace
• Compressor
• Condenser
• Capillary Tube
• Evaporator
E & F
A & C
(See the next page.)
WARNING
• Before replacing any refrigeration component, recover the refrigerant using standard
recovery procedures and equipment.
and high pressure side (tube 2) as shown in figure below.
• When recovering the refrigerant, use the pinch-off tubes at the low pressure side (tube 1)
• High Pressure Switch