10. REFRIGERATION SYSTEM REPAIR

10.1 Repair of Refrigeration System

• When there is a leak, obstruction, or problem in the refrigeration system of the unit, replace

or repair the defective refrigeration component. After replacing any refrigeration component, all

(1) Proper brazing techniques

• When brazing, use a slightly reduced flame. Oxyacetylene is commonly used since it is easy

to verify and adjust the condition of the flame. Unlike gas welding, a secondary flame is used for

brazing. It is necessary to preheat the base metal properly depending on the shape, size, or

thermal conductivity of the brazed fitting.

• The most important point in flame brazing is to bring the whole brazed fitting to a proper brazing

temperature. Care should be taken to not cause overflow of the brazing filler metal, oxidation of

the brazing filler metal, or to not deterioration due to overheating of the flux.

(2) Brazed fittings and fitting clearance

• In general, the strength of the brazing filler

metal is lower than the base metal. Therefore,

the shape and clearance of brazed fitting

are very important. As for the shape of

brazed fitting, it is necessary to maximize its

adhesive area. The clearance of the brazed

fitting must be minimized to facilitate brazing

filler metal to flow into the fitting by capillary

action.

I002225

Clearance

Clearance From The Pipe Fitting and Tubing.

0.001~0.003 in
(0.025~0.075 mm)

a

a

the connections must be brazed.