beautypg.com

5 evaporator, 6 accumulator, 7 high-pressure switch – MovinCool Classic 10 Service Manual User Manual

Page 16: 16 4.5 evaporator

background image

Operation Section

16

4.5 Evaporator

• The evaporator is a heat exchanger covered

with plate fins. Heat is removed from the air

being pulled across the evaporator by the

centrifugal fan. The resulting cool air is

expelled through the cooling air ducts.

4.6 Accumulator

• The accumulator is mounted on the suction

gas piping between the evaporator and the

compressor. The accumulator separates the

liquid refrigerant from the gas refrigerant,

allowing only the gas refrigerant to enter the

compressor. In the accumulator, suction gas is

led into a cylindrical vessel where the speed of

the gas is decreased. This process separates

the refrigerant contained in the gas by the force

of gravity, causing the refrigerant to accumulate at the bottom of the vessel. As a result, the

compressor is protected from possible damage caused by liquid refrigerant intake.

ILL00552-00

I000514

From Evaporator

To Compressor

4.7 High-Pressure Switch

• The high-pressure switch prevents the

condenser and compressor from being

damaged by excessive high pressure in the

high-pressure line of the refrigeration cycle.

The switch is normally closed. The snap disk

responds to the variations in pressure and, if

pressure is abnormally high, the snap disk

moves down to push the pin down, causing the

internal contacts to open. This interrupts the

ground signal at the relay board which turns the compressor off.

I001768

Pressure of Refrigerant

Movable Point

Snap Disk

Pin

Terminal

Lead Wires

Stationary Point

Molding by Resin

Case

This manual is related to the following products: