Operation Section

27

5.4 Compressor

(1) Compressor motor

• The compressor motor is a single-phase motor

and is contained within the same housing as

the compressor.

(2) Compressor overload relay

• An external compressor overload relay is used

to protect the compressor motor. This relay is

mounted within the connector housing that

attaches to the top of the compressor. The

relay interrupts the flow of current when there

is an overload condition such as high current

draw and/or high temperature build up in the

compressor.

Operating Temperature

Non-Operating Limit at 212 °F

(100 °C)

Marking

OFF (Open Contacts)

ON (Closed Contacts)

302 °F (150 °C)

142 °F (61 °C)

12.8 A

MRA1261-12026

I002355

I001691

Bimetal

Terminal

Points

Specifications:

Rated Voltage

115 V

Rated Output

700 W