beautypg.com

MovinCool Classic 10 Service Manual User Manual

Page 44

background image

Repair Section

44

(2) For unit serial number from April 2011 (0411) to Present

• Measure resistance across the terminals of the

fan motor.

• If the measured resistance is not equal to the

standard values listed above, replace the fan

motor.

ILL00562-00

CF2

CF1

CN21

Resistance at 68 °F (20 °C)

CF1 - CN21-3

CF2 - CN21-3

Approx. 8.2 ohm

Approx. 9.8 ohm

8.7 Capacitor Inspection (For Fan Motor and Compressor)

(1) Ohmmeter method

• Set the ohmmeter to the 10 M ohm range.

Place the two probes against the two terminals

of the capacitor. At first, the ohmmeter

indicates small value, then the reading should

gradually increase towards infinity (

),

indicating that the capacitor is charging. If the

reading indicates infinity immediately (open),

or the ohmmeter fails to move from 0 ohm

(shorted), replace the capacitor.

(2) Capacitance tester method

WARNING

• Properly discharge the capacitor(s) before and after testing. Failure to discharge the

capacitor may cause damage to the test equipment and/or unit, and result in personal

injury (electrical shock) or death.

Unit Serial Number

Capacitor

Rated

Voltage

Capacitance

From February 2011 (0211)
to March 2011 (0311)

For Fan Motor

450 V

10

μF

For Compressor

450 V

55

μF

ILL00567-00

Use a capacitance tester to check the capacitors for the values indicated below. If the value tested

is not within 10% of the indicated capacitance, replace the capacitor.

From April 2011 (0411)
to Present

For Fan Motor

250 V

25

μF

For Compressor

450 V

55

μF