Repair Section
55
1) Loosen the set screw with a hex key, and then
remove the condenser fan.
CAUTION
• Set Screw Torque Value (for Installation)
- 10.80 ± 2.17 ft•lbf (14.7 ± 3.0 N•m)
2) Take off the thee (3) nuts, and then remove the
condenser fan housing.
3) Take off the four (4) nuts, and then remove the
fan motor together with the motor bracket.
4) Loosen the set screw with a hex key, and then
remove the evaporator fan.
I002361
Condenser Fan
Set Screw
ILL00573-00
Nuts (3)
Housing for
Condenser
Fan
ILL00574-00
Fan Motor
Nuts (4)
Motor Bracket
I001740
Evaporator Fan
Set Screw