MovinCool Classic 10 Service Manual User Manual
Page 34

Operation Section
34
(2) Fan only mode
• When the FAN button on the control panel is pressed, the FAN “ON” LED illuminates, and the
fan operates. At this time, the compressor is off, and only the fan is in operation. When the FAN
button is pressed again, the fan stops.
(3) Cool mode
• When the COOL ON/OFF button is pressed, the FAN “ON” LED illuminates, and room
temperature is shown on the display. At this time, the compressor and fan begin to operate to
provide cooling. When the COOL ON/OFF button is pressed again, the compressor and fan
stop.
• When the COOL ON/OFF button is pressed in fan only mode, room temperature is shown on
the display, and the compressor operates to provide cooling. If room temperature reaches the
set temperature during cooling operations, the compressor stops, and only the fan continues to
operate. (Fan operate mode is a default setting from the manufacturer.)
< NOTE >
The fan only mode will not operate after the cool mode has been activated. Once the cool mode
is activated, the unit cannot be turned off by pressing the fan button. Rather, the COOL ON/OFF
button must be pressed.
*Fan stop mode
- In fan stop mode, if room temperature reaches the set temperature during cooling operations,
both the compressor and fan stop. The fan stop mode setting can be changed using the dip
switch on the relay board. (For details, refer to page 23). During cooling operations when in
the fan stop mode, the FAN “AUTO” LED illuminates.
(4) Change temperature mode “°C” and “°F”
• The temperature display can be switched between “°C” and “°F” by holding the SET TEMP
arrow buttons ( ,
) and the FAN button down simultaneously for 3 seconds.
(5) Diagnostic code
• Most of the diagnostic codes can be RESET by holding the SET TEMP arrow buttons (
,
)
down simultaneously for 3 seconds. (For details, refer to page 35 to 36.)